Level spreader: how the PA BMP Manual describes it
Quick answer: In the Pennsylvania Stormwater Best Management Practices Manual, BMP 6.8.1 is a level spreader that turns concentrated runoff into sheet flow over stabilized vegetation. It must be perfectly level, belongs only on undisturbed ground, and is not a sediment-removal practice.
What it is
The manual says a level spreader distributes concentrated runoff as sheet flow to reduce erosive energy. It says there are essentially two categories: inflow spreaders, which evenly feed another BMP such as a filter strip or infiltration basin (concrete sills, curbs, earthen berms), and outflow spreaders, such as a level perforated pipe in a shallow aggregate trench. A stand-alone spreader can dissipate runoff from a roof or other impervious area. Performance is rated Low across the board, with 20% for TSS, 10% for phosphorus and 5% for nitrate.
Key design numbers
| Item | What the manual says |
|---|---|
| Design flow | At least the 10-year/24-hour peak; flows above can bypass |
| Length | Minimum 10 feet, maximum 200 feet |
| Grass or thick cover | 13 linear feet per 1 cfs, slope 8% or less |
| Forested, little ground cover | 100 linear feet per 1 cfs, slope 6% or less |
| Receiving area | Undisturbed or stabilized, minimum flow length 75 feet |
| Perforated pipe | 4 to 12 inches in diameter in an AASHTO No. 57 stone envelope |
| Pipe depth | Shallow, with a 12-inch layer of No. 57 stone |
| Pipe safety factor | Minimum 1.1 on pipe length |
The manual’s worked example uses a 2 cfs ten-year flow and a 5 cfs hundred-year flow with 12-inch pipe, thirty-six 0.375-inch perforations per foot, and gets 24 feet and 59 feet. Do not place a spreader in constructed fill, and avoid initially concentrating runoff by using as many outfalls as possible. Matting or compost blanketing is recommended downhill.
Where it fits and where it does not
The manual says level spreaders are not applicable where soils erode easily or vegetation is sparse, and that site topography, vegetation, soil and geology must be considered first. Rigid inflow structures are preferred over earthen berms, which can erode, and multiple outfalls are preferred over a single outfall. Typical applications are the ultimate outlet from a structural BMP that does not discharge directly to a stream, roof downspout connections and inlet connections, each under 500 square feet of impervious area for the stand-alone case. A pipe spreader should handle at least the 10-year storm and may handle the 100-year storm if space permits. Stand-alone spreaders mainly give limited volume or rate reduction, with some water quality benefit.
Construction and maintenance
Stabilize uphill development before diverting runoff, install all contributing elements, then lay the pipe along a contour with a level bottom. Maintenance is quarterly inspection for two years, then twice a year and after storms over 1 inch. Standing water must not persist beyond 72 hours. Inspect vegetation every two weeks through the first growing season, maintain 85% cover, and replace it if damage exceeds 50%. The manual’s old cost range, with no year stated, is $5 to $20 per foot, with concrete costing significantly more than pipe or berms.
Where the manual contradicts itself
- The 500 square foot threshold: stand-alone credit is described for impervious areas greater than 500 square feet in one place and areas of 500 square feet or less in another.
- Stone size: design and construction call for AASHTO No. 57 stone, while the specification calls for 2-inch to 1-inch stone labeled AASHTO size number 3.
- Category count: two categories are named, but the variations list three types.
- Safety factor: the worked example does not apply the 1.1 factor, which would lengthen it to about 26 and 65 feet.
- Design storm: the 10-year storm in the key elements becomes the 10-year/24-hour storm in the design considerations.
Pennsylvania approvals and who designs it
Sizing, level survey and the receiving-area slope check need a qualified professional such as a licensed engineer. A level spreader used for stormwater control may need approval from your municipality, the county conservation district or DEP. Check PA stormwater plan rules, Chapter 102 and Pennsylvania drainage law before directing flow toward a neighbor.
Sources
- Pennsylvania Department of Environmental Protection, Pennsylvania Stormwater Best Management Practices Manual (363-0300-002, December 30, 2006), BMP 6.8.1 Level Spreader, via the PA DEP eLibrary (greenport.pa.gov). Checked Nov 23, 2026.
Related
All drainage guides · Vegetated filter strip · Infiltration berm · Infiltration basin
FAQ
How long can a level spreader be?
The PA BMP Manual gives a minimum of 10 feet and a maximum of 200 feet.
What storm must it handle?
At least the 10-year/24-hour peak; the manual allows larger flows to bypass if space is limited.
Can it go on fill?
No. The manual says not to place it in constructed fill, because virgin soil resists erosion better.
Does it remove sediment?
The manual says it is not for sediment removal and lists only 20% TSS, 10% phosphorus and 5% nitrate.
Planning information only. Design must be done by a qualified professional and approved by your municipality and, where required, DEP. Source checked Nov 23, 2026.