Home / PA site regulations / Job site fire protection

Fire protection on job sites: OSHA 1926.150

Quick answer: OSHA requires an employer to maintain a fire protection program for all phases of construction and demolition. Under 29 CFR 1926.150, that includes portable extinguishers, such as one rated at least 2A for each 3,000 square feet of protected building area, with no more than 100 feet of travel to the nearest one.

Where the rules live

Fire protection on construction sites is covered by Subpart F of 29 CFR Part 1926. The general safety provisions in Subpart C add a short rule in 1926.24: the employer must maintain an effective fire protection and prevention program at the job site throughout all phases of construction, repair, alteration or demolition work, and must make sure the fire protection and suppression equipment required by Subpart F is available. Section 1926.150 then spells out what that equipment and program include. This page summarizes the eCFR text for homeowners, general contractors and crew leads. Fire prevention rules for storage and ignition sources are in 1926.151, and flammable liquids are in 1926.152. Both are covered on separate pages.

Use Table F-1 in the current regulation when choosing an extinguisher class for a specific hazard.

The fire protection program

Section 1926.150(a) sets the baseline.

  • The employer must maintain a fire protection program for all phases of construction and demolition.
  • Firefighting equipment must be provided without delay as fire hazards arise.
  • Equipment must stay accessible at all times and be conspicuously located.
  • Equipment must be inspected periodically and kept operational. Defective equipment must be replaced immediately.
  • Where warranted, the employer must provide a trained and equipped fire brigade.

Water supply

Under 1926.150(b), the water supply must be sufficient in volume, duration and pressure, and must be available as soon as combustible materials accumulate on the site. Underground water mains must be installed and made usable as soon as practicable.

Portable extinguishers and substitutes

ItemWhat 1926.150(c) says
Basic coverageOne extinguisher rated at least 2A for each 3,000 square feet of protected building area, or major fraction of it
Travel distanceNo more than 100 feet to the nearest extinguisher
Per floorAt least one 2A extinguisher per floor; in multistory buildings, at least one adjacent to a stairway
Flammable liquids or gasA 10B extinguisher within 50 feet wherever more than 5 gallons of flammable or combustible liquids or 5 pounds of flammable gas are used; this does not apply to integral fuel tanks of motor vehicles
FreezingExtinguishers and water drums subject to freezing must be protected from freezing

The rule allows some substitutes for a 2A extinguisher. A 55-gallon open drum of water with two fire pails may stand in. So may a half-inch garden-type hose up to 100 feet long with a nozzle, if it discharges at least 5 gallons per minute with a horizontal stream range of at least 30 feet, and if it is kept on racks or reels with enough hose stations that one stream reaches every point in the area. For hose and connections, up to 100 feet of 1 1/2-inch hose with a nozzle discharging at least 25 gallons per minute can substitute for an extinguisher rated 2A or less, if it reaches all points in the area. Adapters must be provided where hose connections do not match local fire equipment.

Several further rules apply to extinguishers themselves. Carbon tetrachloride and other toxic vaporizing liquid extinguishers are prohibited. Extinguishers must be inspected periodically and maintained in line with NFPA 10A-1970, and they must be listed or approved by a nationally recognized testing laboratory. During demolition that involves combustible materials, charged hose lines from hydrants, pumped tank trucks or equivalent sources must be available.

Fixed equipment: sprinklers and standpipes

Section 1926.150(d) covers permanent systems in buildings under construction. Sprinkler installation must closely follow construction and be placed in service as soon as applicable laws permit after each story is completed. During demolition or alteration, existing sprinkler systems must stay in service as long as reasonable, and only authorized persons may operate the control valves. Sprinkler control valves must be checked daily at the close of work. Standpipes must be brought up as soon as applicable laws permit and kept ready for use. Siamese fire department connections must be on the outside at street level and conspicuously marked, and there must be at least one standard hose outlet per floor.

Alarms and fire cutoffs

An alarm system, such as a telephone or siren, must be established to alert employees on the site and the local fire department, according to 1926.150(e). Alarm codes and reporting instructions must be posted at telephones and at employee entrances. Under 1926.150(f), fire walls and exit stairways that the completed building will require are to be given construction priority, fire doors with automatic closers must be hung as soon as practicable, and fire cutoffs must stay in buildings under alteration or demolition until operations require their removal.

Why it matters on landscape and site jobs

The standard is written for construction in general, including work in and around structures. Many crews run fuel-powered saws, compactors, mini excavators and generators, and the 10B extinguisher rule is keyed to how much flammable liquid or gas is in use, not to the size of the company. The reference to a 5-gallon threshold for liquids and 5 pounds for flammable gas is the number a crew lead can check against what is actually on the truck or trailer. Motor vehicle integral fuel tanks are excluded from that rule.

Common mistakes

  • Letting an extinguisher sit where it is not conspicuous or accessible.
  • Failing to inspect equipment periodically, or leaving a defective unit in service.
  • Storing water drums or extinguishers where they can freeze.
  • Using an extinguisher that is not listed or approved by a nationally recognized testing laboratory.
  • Posting no alarm code or reporting instructions at the telephone.
  • Forgetting the 10B extinguisher requirement where more than 5 gallons of flammable liquid is in use.

When to get professional help

This page covers only part of Subpart F. Choosing the right extinguisher class, designing a sprinkler or standpipe system, or setting up a fire brigade is work for a qualified fire protection or safety professional, and the local fire marshal or fire department can advise on local requirements. A written program should come from a qualified safety professional or OSHA’s consultation resources.

Sources

Sources checked Nov 23, 2026.

Related

First aid and medical services · Job site electrical safety · Hazard communication · All PA site work regulations

Talk to us about your project

FAQ

How many fire extinguishers does OSHA require on a construction site?

Under 1926.150(c), one rated at least 2A for each 3,000 square feet of protected building area or major fraction of it, with a maximum travel distance of 100 feet to the nearest extinguisher.

When is a 10B extinguisher required?

A 10B extinguisher must be within 50 feet wherever more than 5 gallons of flammable or combustible liquids or 5 pounds of flammable gas are used, other than integral fuel tanks of motor vehicles.

Can a hose replace a fire extinguisher?

Section 1926.150(c) allows a half-inch garden-type hose up to 100 feet long to substitute for a 2A extinguisher if it discharges at least 5 gallons per minute with a horizontal stream range of at least 30 feet and one stream reaches all points in the area.

Who must have a fire alarm system on a site?

Section 1926.150(e) requires an alarm system, such as a telephone or siren, that alerts employees on the site and the local fire department, with alarm codes and reporting instructions posted.