Home / PA site regulations / Job site electrical safety

Job site electrical safety: GFCIs, cords and energized lines

Quick answer: OSHA’s construction electrical rules are in 29 CFR 1926 Subpart K. Employers must protect workers on temporary power with either ground-fault circuit interrupters (GFCIs) or an assured equipment grounding conductor program, check for energized circuits before work starts, and keep worn or frayed cords out of use.

What Subpart K covers

Section 1926.402 says Subpart K applies to temporary and permanent electrical installations used on the jobsite. It does not cover existing permanent installations that were in place before construction began. For landscape, hardscape and excavation crews, the parts that come up most are temporary power from a generator or a customer’s outlet, extension cords for tools and lights, and digging or working near power lines. This page covers sections 1926.402 through 1926.408, sections 1926.416 and 1926.417, and sections 1926.431 through 1926.449.

Ground-fault protection: 1926.404(b)

For temporary wiring on construction sites, the employer must use either GFCIs or an assured equipment grounding conductor program.

  • GFCIs: Required on 120 volt, single-phase, 15- and 20-ampere receptacles on construction sites that are not part of the permanent wiring of the building and are in use by employees. A two-wire generator rated 5 kW or less may be exempt if its conductors are insulated from the frame and other grounded surfaces.
  • Assured equipment grounding conductor program: The employer needs a written description available at the jobsite and a designated competent person. Cords, plugs and receptacles must be visually inspected before each day’s use. Equipment grounding conductors must be tested for continuity, and receptacle and plug grounding connections must be checked.

Under the assured grounding program, tests are required before first use, after repairs, after a suspected damaging incident, and at intervals not exceeding 3 months, or 6 months for fixed cords and receptacles not exposed to damage. Test records must be kept and be available on the jobsite. Confirm the exact paragraph wording in the full text before writing a program.

The definitions in 1926.449 describe a ground-fault circuit interrupter as a device that deenergizes a circuit when the current to ground exceeds a set value, to protect personnel.

Before work starts: 1926.416

Section 1926.416 is general requirements. Its key points:

  • Protection near power circuits: Employees near power circuits must be protected by deenergizing and grounding the circuit, or by guarding it with insulation or other means.
  • Underground lines: Where line locations are unknown, employees using jackhammers, bars or similar hand tools that may contact a line must have insulated protective gloves.
  • Pre-work survey: Before work begins, the employer must check for energized circuits that could contact people, tools or machines. Warning signs must be posted, and employees must be told the line locations, hazards and protective measures.
  • Cords and cables: Worn or frayed cords may not be used, and extension cords may not be stapled, hung from nails or suspended by wire.
  • Passageways: Barriers must keep an electrical workspace from being used as a passageway when energized parts are exposed, and cords must be kept clear of working spaces and walkways.

The underground line rule is the one an excavation or fence crew should think about. It does not replace locating utilities before digging. For Pennsylvania, see our page on PA One Call notice basics.

Lockout and tagging of circuits: 1926.417

Controls deactivated during work on equipment or circuits must be tagged. Deenergized equipment or circuits must be rendered inoperative and tagged wherever they could be energized, and tags must plainly identify the equipment or circuits being worked on.

Clearances and working space

Section 1926.403 sets working clearances for equipment at 600 volts or less. For 0 to 150 volts the clearance is 3 feet, and at 151 to 600 volts it is 3 feet, 3.5 feet or 4 feet depending on the condition. Working space is at least 30 inches wide, and headroom at service equipment, switchboards, panelboards or motor control centers is at least 6 feet 3 inches. Live parts at 50 volts or more must be guarded, for example by enclosures or by being 8 feet or more above the working surface.

For outdoor open conductors of 600 volts or less, 1926.404(c)(1) lists minimum clearances that include 10 feet above grade or walkways, 12 feet over non-truck vehicle areas, 15 feet over other truck areas and 18 feet over public streets and driveways. Conductors must be at least 3 feet from windows and doors. These are installation clearances for wiring, not a substitute for the distances required when equipment works near utility lines.

Grounding and the environment

Section 1926.404(f) includes grounding rules. As one example, noncurrent-carrying metal parts within 8 feet vertically or 5 feet horizontally of grounded objects and subject to employee contact must be grounded. Section 1926.432 says that unless identified for the environment, conductors and equipment may not be placed in damp or wet locations, in areas with deteriorating agents, or at excessive temperatures, and equipment meant only for dry locations must be protected from the weather during construction.

Scaffolds and aerial lifts near power lines

Separate clearance distances apply to scaffolds in Subpart L: uninsulated lines of 50 kV or less require 10 feet, insulated lines under 300 volts require 3 feet, and insulated lines from 300 volts to 50 kV require 10 feet. See our page on scaffold and aerial lift basics. This page gives no distances for overhead power line clearances for cranes or other equipment.

Common mistakes

  • Plugging tools into a temporary outlet with no GFCI and no grounding program.
  • Using a cord with a cracked jacket, exposed conductors or a missing ground pin.
  • Stapling or nailing a cord to a post or hanging it from a nail.
  • Leaving cords across walkways where they get run over.
  • Starting a dig or lift without checking for energized lines.
  • Skipping the daily visual cord check under an assured grounding program.

When to get professional help

Electrical work on service equipment, panels and wiring belongs with a licensed electrician. A written grounding program, a utility clearance plan or an incident review should come from a qualified safety professional or OSHA’s consultation resources. If a line is down or a worker is in contact with a line, call 911 and the utility.

Sources

Sources checked Nov 23, 2026.

Related

Hand and power tool safety · PA One Call basics · OSHA trench protection basics · All PA site work regulations

Talk to us about your project

FAQ

Do I need a GFCI on a construction site?

Section 1926.404(b) requires either GFCIs or an assured equipment grounding conductor program. GFCIs are required on 120 volt, single-phase, 15- and 20-ampere receptacles that are not part of the permanent wiring and are in use by employees.

Can I use a frayed extension cord?

No. Section 1926.416 says worn or frayed cords may not be used, and extension cords may not be stapled, hung from nails or suspended by wire.

What must be checked before work near power lines?

Section 1926.416 requires the employer to check for energized circuits that could contact people, tools or machines, post warning signs, and tell employees the line locations, hazards and protective measures.

How often must grounding conductors be tested under an assured program?

Tests are required before first use, after repairs, after a suspected damaging incident, and at intervals not exceeding 3 months, or 6 months for fixed cords and receptacles not exposed to damage.

General information only, not legal or safety advice. Employers must follow the current OSHA standard and applicable Pennsylvania rules. Source pages checked Nov 23, 2026.