Guides · Retaining wall installation · Step 4

Retaining wall drain pipe and outlets

The perforated pipe at the base of the wall collects water from the stone zone and carries it out. If it has nowhere to go, it is just a buried bucket. Here is what the manufacturers and NCMA say about size, slope and outlet spacing.

Quick answer

Lay a perforated pipe low in the drainage stone behind the wall and run it to daylight. Belgard calls for 4- or 6-inch perforated drain tile with an outlet through the wall face every 50 ft. NCMA gives 20 to 50 ft between outlets. Allan Block daylights every 50 ft. Follow your block’s manual for the exact spacing.

Steps

1. Set the pipe low

Belgard places the perforated drain tile low in the stone zone behind the wall and covers it with 3/4-inch rock. Unilock uses a 4-inch perforated pipe.

2. Give it slope

NCMA says secondary pipes need a slope of at least 2%. It names ASTM F758 and F405 for pipe. The pipe must run toward its outlet.

3. Daylight it

Belgard runs an outlet through the wall face every 50 ft. Unilock daylights the pipe at the end of the wall. NCMA spaces outlets 20 to 50 ft apart.

4. Cover with stone

Surround the pipe with clean stone before backfilling. See drainage aggregate.

5. Protect the outlet

Keep the outlet clear of soil, mulch and plants. Point it where water can leave the site without running at a neighbor or a structure.

6. Don’t interrupt it

Allan Block says the drain pipe behind stairs should run uninterrupted. See steps in walls.

Pipe and outlets by source

SourcePipeOutlet
Belgard4- or 6-inch perforated drain tile, low in the stone, covered with 3/4-inch rockThrough the wall face every 50 ft
NCMAMain collection pipe at least 3 in. diameter; secondary pipes at least 2% slope20 to 50 ft apart
Unilock4-inch perforated pipeDaylight at the wall end
Allan BlockRequired for reinforced walls, gravity walls over 4 ft, and poor drainageDaylight every 50 ft

The sources reviewed do not give a pipe-slope figure for the main run beyond NCMA’s 2% for secondary pipes. Check your manual or design.

Planning information, not engineering advice. Where the outlet discharges can be regulated, especially near a property line or a stream. Check local rules and have an engineer size drainage for tall walls or wet sites. See when a wall needs an engineer.

Questions

Does every retaining wall need a drain pipe?

Allan Block calls for one on reinforced walls, gravity walls over 4 ft, and walls with poor drainage. Other sources show it as standard practice. Your design and local code decide.

How often should the pipe outlet?

Belgard and Allan Block say every 50 ft. NCMA gives 20 to 50 ft between outlets.

What size drain pipe is used?

Belgard uses 4- or 6-inch perforated pipe, Unilock uses 4-inch, and NCMA calls for a main collection pipe of at least 3 in.

Which way do the holes face?

The pages reviewed do not state hole orientation. Follow the pipe maker’s and block maker’s instructions.

Sources: Belgard SRW Quick Reference Install Guide (2023); Unilock, How to Build Retaining Walls; NCMA retaining wall installation guide; Allan Block, Basic Installation and Stairs in a Retaining Wall. Checked Nov. 22, 2026.