Flammable liquids on job sites: OSHA 1926.152 storage and handling
Quick answer: OSHA’s flammable liquids rule, 29 CFR 1926.152, requires approved safety cans or DOT containers for quantities of 5 gallons or less, and no more than 25 gallons of flammable liquid in a room outside an approved storage cabinet. These limits apply to liquids with a flashpoint at or below 199.4 degrees F.
Where the rules live
Flammable and combustible liquids on construction sites are covered by 29 CFR 1926.152 in Subpart F. The rule applies to liquids with a flashpoint at or below 199.4 degrees F (93 degrees C), and it excludes bulk transportation of flammable liquids and fuel oil tanks connected to oil-burning equipment. Any fuel or solvent in that range, kept on a trailer, in a shed or in a building under construction, falls under the rule. This page summarizes the eCFR text for homeowners, general contractors and crew leads. It sticks to the container, storage and dispensing rules that apply to most small jobs, and leaves out the detailed bulk tank, piping and marine service station provisions.
How the rule sorts flammable liquids
Section 1926.155 defines a flammable liquid as one with a vapor pressure of 40 psia or less at 100 degrees F and a flash point of 199.4 degrees F or below, and splits them into four categories.
| Category | Flash point and boiling point |
|---|---|
| Category 1 | Flash point below 73.4 degrees F and boiling point at or below 95 degrees F |
| Category 2 | Flash point below 73.4 degrees F and boiling point above 95 degrees F |
| Category 3 | Flash point from 73.4 degrees F to 140 degrees F |
| Category 4 | Flash point above 140 degrees F to 199.4 degrees F |
A safety can, in the same section, is an approved closed container of 5 gallons or less with a flash-arresting screen, a spring-closing lid and spout cover, and an internal design that safely relieves pressure when exposed to fire.
Containers
Under 1926.152(a), only approved containers and portable tanks may be used for storage and handling of flammable liquids. Approved safety cans or Department of Transportation approved containers must be used for handling and use of flammable liquids in quantities of 5 gallons or less. There are two exceptions: a very viscous liquid may stay in its original shipping container, and containers of 1 gallon or less may use the original container. Flammable liquids may not be stored in exits, stairways or normal passageways.
Storage inside buildings
Section 1926.152(b) limits how much can sit in a room. No more than 25 gallons of flammable liquid may be stored in a room outside an approved storage cabinet. Larger quantities go in an acceptable or approved cabinet or an inside storage room.
- Cabinets: a wooden cabinet must be built of exterior-grade plywood at least 1 inch thick, with rabbeted joints fastened in two directions with flathead wood screws, a door overlap of at least 1 inch, steel hinges, and fire-retardant paint inside and out. Approved metal cabinets are also acceptable. Every cabinet must be labeled “Flammable-Keep Away from Open Flames.”
- Cabinet limits: no more than 60 gallons of Category 1, 2 and 3 liquids or 120 gallons of Category 4 liquids in one cabinet, and no more than three cabinets in a storage area. Larger amounts must go to an inside storage room.
- Inside storage rooms: these must be fire-resistive construction, with electrical equipment approved for Class I, Division 1 locations, exhaust ventilation starting no more than 12 inches above the floor and designed for at least 6 complete air changes per hour, and one clear aisle at least 3 feet wide. Containers over 30 gallons may not be stacked.
- Near spraying: the quantity of flammable liquid kept near a spraying operation should be the minimum needed, ordinarily no more than one day’s or one shift’s supply.
Storage outside buildings
| Item | What 1926.152(c) says |
|---|---|
| Container size | Containers up to 60 gallons each |
| Pile size | No more than 1,100 gallons in any one pile or area |
| Spacing | 5 feet between piles; piles at least 20 feet from buildings |
| Access | A 12-foot-wide access way within 200 feet of each pile |
| Spill control | Grading to divert spills away from buildings or other storage, or a curb or dike at least 12 inches high |
| Portable tanks | At least 20 feet from buildings, with a 12-foot access way within 200 feet |
Outdoor storage areas must also be kept free of weeds, debris and other unnecessary combustible material.
Fire control around storage
Section 1926.152(d) calls for a fire extinguisher rated at least 20-B outside, within 10 feet of the door to any room storing more than 60 gallons of flammable liquid. A 20-B extinguisher must also be located 25 to 75 feet from any outdoor flammable liquid storage area. Tank trucks and other vehicles that transport or dispense flammable liquids must carry a 20-B:C extinguisher.
Dispensing and use
Transfers of more than 5 gallons at one time must be separated from other operations by 25 feet or by 1-hour fire-resistant construction, with spill drainage and ventilation that keeps the vapor at or below 10 percent of the lower flammable limit (1926.152(e)). Transfers of Category 1, 2 or 3 liquids are allowed only when the containers are bonded. Transfers must be made through closed piping, from safety cans, by a top-drawing device, or by gravity or pump through an approved self-closing valve, and air-pressure transfer is prohibited.
At the point of use (1926.152(f)), Category 1, 2 and 3 liquids must be kept in closed containers when not in use, leaks and spills must be cleaned up promptly and safely, and these liquids may be used only where there are no open flames or other ignition sources within 50 feet, unless conditions warrant more clearance.
Service and refueling areas
For fueling and service areas, 1926.152(g) requires approved closed containers, underground tanks or aboveground portable tanks, an approved dispensing hose, and an automatic-closing nozzle with no latch-open device. There must be no smoking or open flames in fueling or dispensing areas, conspicuous no-smoking signs, and vehicle motors shut off during fueling. A 20-B:C extinguisher must be within 75 feet of each pump, dispenser, underground fill opening and service area.
Common mistakes
- Keeping more than 25 gallons of flammable liquid in a room outside an approved cabinet.
- Handling 5 gallons or less in something other than an approved safety can or DOT container.
- Leaving a container in an exit, stairway or passageway.
- Fueling with the motor running or with an open flame nearby.
- Storing drums closer than 20 feet to a building.
- Skipping bonding when transferring Category 1, 2 or 3 liquids.
When to get professional help
This page covers only part of 1926.152. Bulk tanks, inside storage rooms, dispensing systems and underground tanks should be designed and inspected by a qualified professional, and the local fire marshal can advise on local fire code. A written hazard program should come from a qualified safety professional or OSHA’s consultation resources.
Sources
Sources checked Nov 23, 2026.
Related
Fire protection and extinguishers · Fire prevention and storage · Hazard communication for landscape chemicals · All PA site work regulations
FAQ
How much flammable liquid can be stored in a room under OSHA?
Section 1926.152(b) says no more than 25 gallons of flammable liquid may be stored in a room outside an approved storage cabinet.
What container must be used for 5 gallons or less of flammable liquid?
Approved safety cans or Department of Transportation approved containers must be used for handling and use of quantities of 5 gallons or less, with the exceptions in 1926.152(a).
How far must outdoor flammable liquid storage be from buildings?
Containers stored outside must be in piles at least 20 feet from buildings, with 5 feet between piles, under 1926.152(c).
Is air pressure allowed to transfer flammable liquids?
No. Section 1926.152(e) prohibits air-pressure transfer of flammable liquids.
General information only, not legal or safety advice. Employers must follow the current OSHA standard and applicable Pennsylvania rules. Source pages checked Nov 23, 2026.