How Deep Should Footings Be? Depth and Size for Decks, Garages and Houses

Every footing goes at least 12 inches below undisturbed ground, and houses, attached garages and decks attached to the house also go below the local frost line. Size comes from the soil and how much load each footing carries, and the IRC tables give the minimums.

How deep should footings be? Under the International Residential Code, every footing goes at least 12 inches below undisturbed ground, and footings for houses, additions, attached garages and decks attached to the house also go below the local frost line. Small detached buildings and freestanding decks can skip the frost line under the model code, but your building department has the final say.

Quick answer

Every exterior footing goes at least 12 inches below undisturbed soil. Anything tied to the house also goes below the frost line your jurisdiction sets. Size depends on soil and load: a house wall footing is at least 12 inches wide and 6 inches thick, and a round deck post footing runs from 8 to 31 inches across at a 40 psf live or snow load, depending on how much deck the post carries.

12 inminimum depth into undisturbed soil
12 x 6 insmallest wall footing, width by thickness
600 sq ftdetached light-frame buildings this size or smaller skip frost depth
16 inround deck footing for 40 sq ft of deck on clay

The two depth rules every footing follows

The first rule is a flat minimum: IRC Section R403.1.4 puts exterior footings at least 12 inches below the undisturbed ground surface, and Section R507.3.2 sets the same 12 inches for deck footings.

The second rule is frost. Section R403.1.4.1 says foundations, piers and other permanent supports must be protected from frost by one of four methods: going below the frost line, a frost-protected shallow foundation, an ASCE 32 design, or bearing on solid rock. Footings can’t bear on frozen soil unless it stays frozen.

The code doesn’t print one frost depth for the country. Table R301.2 leaves a blank that each jurisdiction fills in with the minimum depth of footing below finish grade. Our guide to frost line depth by state shows which states print a number and how to find yours.

Whichever rule gives the deeper hole wins, and the bottom has to land on undisturbed natural soil or engineered fill, per Section R403.1, not on topsoil or loose backfill.

Footing depth by structure

StructureDepthFrost protection?Size rule
House, addition or attached garage12 in. minimumYesTable R403.1(1), never under 12 x 6 in.
Detached garage or shed over 600 sq ft (light frame)12 in. minimumYesTable R403.1(1)
Detached light-frame accessory building (garage, shed), 600 sq ft or less, eaves 10 ft or lower12 in. minimumNot requiredTable R403.1(1)
Deck attached to the house12 in. minimumYesTable R507.3.1
Freestanding deck12 in. minimumNot required by R507.3.3Table R507.3.1
Freestanding deck on pier blocks, 200 sq ft or less, 20 in. high or lessNo footing requiredNoPrecast pier blocks at grade
2021 IRC. For buildings other than light frame, the frost exemption drops to 400 sq ft. Local codes can be stricter.
Which footings go below the frost line Which footings go below the frost line 2021 IRC minimums, measured to the bottom of the footing House, addition, attached garage Deck attached to the house Freestanding deck Detached shed or garage ≤ 600 sq ft* Finished grade 12 in. minimum into undisturbed soil Local frost line set by your jurisdiction Below frost line 12 x 6 in. or wider Below frost line size by deck area 12 in. min. frost rule doesn’t apply 12 in. min. frost exempt* * Light-frame building, 600 sq ft or less, eaves 10 ft or lower (400 sq ft for other construction). Freestanding decks aren’t held to the frost rule in IRC R507.3.3. All footings: 12 in. minimum. Your building department can require more. Confirm before you dig. muthlerlandscaping.com
Every footing goes at least 12 inches into undisturbed soil. Houses, attached garages and decks attached to the house also go below the frost depth your building department sets.

Deck footings

Section R507.3.3 requires frost protection where a deck is attached to a frost-protected structure, usually the house. If frost lifts the posts while the house stays put, the ledger connection takes the strain. A deck that stands on its own isn’t covered by that rule, though its footings still go 12 inches deep. Your building department can still require frost depth for a freestanding deck, so ask before you dig.

Section R507.3 drops footings entirely for two kinds of freestanding deck: joists resting on grade along their full length, or joists sitting directly on precast pier blocks with no beams or posts, 200 square feet or smaller, with the walking surface no more than 20 inches above grade at any point within 36 inches of the edge. Our freestanding deck plans guide covers how those are framed.

Garages, sheds and houses

An attached garage follows the house rules. A detached light-frame garage or shed can skip frost protection if it’s 600 square feet or smaller with eaves 10 feet high or less (400 square feet if it isn’t light-frame); anything bigger goes below the frost line or uses another approved frost method. Our foundation digging guide covers excavating for slabs, garage pads and pole barns.

Pergolas and retaining walls are different jobs. Pergola posts need real footings, explained in our article on anchoring a pergola to pavers, and segmental walls sit on a compacted stone pad, covered in our retaining wall base depth guide.

How big a footing should be

Depth keeps frost from moving a footing. Width keeps the soil from being overloaded. When nobody has tested the soil, the IRC assumes the bearing values in Table R401.4.1: 1,500 pounds per square foot for clay and silt, 2,000 for sand and clayey or silty gravel, 3,000 for sandy gravel and gravel, and more for rock. If the building official expects soil weaker than 1,500, a soils investigation sets the number.

Wall footings for houses and garages

Section R403.1.1 sets the floor: at least 12 inches wide and 6 inches thick, with the footing projecting at least 2 inches past the wall but not more than its thickness. Table R403.1(1) adds width for heavier buildings on weaker soil.

Light-frame building1,500 psf (clay)2,000 psf (sand)3,000 psf (gravel)
1 story, slab on grade12 x 6 in.12 x 6 in.12 x 6 in.
1 story with basement16 x 6 in.12 x 6 in.12 x 6 in.
2 story with crawl space15 x 6 in.12 x 6 in.12 x 6 in.
2 story with basement19 x 6 in.14 x 6 in.12 x 6 in.
IRC Table R403.1(1) at 20 psf roof live load or 25 psf ground snow load, for a 32-foot-wide building. Heavier snow needs more: a one-story slab-on-grade building on clay goes to 14 x 6 in. at 70 psf.

Deck post footings

Deck footings are sized by tributary area: the square feet of deck surface each post holds up. Table R507.3.1 gives the minimum footing for each area and soil.

Deck area per postClay, 1,500 psfSand, 2,000 psfGravel, 3,000 psf or more
20 sq ft12 in. round, 6 in. thick9 in., 6 in.8 in., 6 in.
40 sq ft16 in., 6 in.14 in., 6 in.12 in., 6 in.
60 sq ft19 in., 6 in.17 in., 6 in.14 in., 6 in.
80 sq ft22 in., 7 in.19 in., 6 in.16 in., 6 in.
100 sq ft25 in., 8 in.21 in., 6 in.17 in., 6 in.
160 sq ft31 in., 11 in.27 in., 9 in.22 in., 7 in.
Round footing diameter and thickness at a 40 psf live or ground snow load, from IRC Table R507.3.1. Heavier snow loads use larger sizes from the same table.

Here’s how to find the area. Say the joists run 10 feet from the house ledger to a beam, with posts every 8 feet and no overhang. The ledger carries half the joist load and the beam carries the other half, so a middle post supports 5 by 8 feet, or 40 square feet. On clay that’s a 16-inch round footing. The end posts carry half as much, 20 square feet, so 12 inches works.

What size Sonotube for a 6×6 post

Table R507.3.1 sizes the footing, the concrete that bears on the soil, not the tube. If you pour a straight tube with nothing wider at the bottom, the tube’s diameter is your footing size and it has to meet the table.

That gets tight fast. Sonoco’s Builder’s Tube comes in 6, 8, 10 and 12 inch diameters, and Sonoco notes those sizes are nominal, so measure if it matters. At a 40 psf load, a straight 12-inch tube covers about 20 square feet of deck on clay and 40 on gravel. A post holding more deck than that needs a wider footing.

The usual fix is a wider footing at the bottom of the hole with the tube on top as a pier. The footing gets the bearing area, and the tube only has to fit the post and its hardware.

The code also says the footing must give the post complete bearing. A square post is wider across its corners than across a face, so a 6-inch tube is too small for a 6×6 to sit on. Measure your post corner to corner and buy the tube bigger than that.

Builder’s note: An auger leaves loose soil in the bottom of the hole, and loose soil settles under load. Scrape it out until you’re on firm, undisturbed ground before you pour, and if the bottom is soft, wet or full of old fill at the required depth, stop and ask the inspector before adding concrete.

Mini excavator digging on a residential job in Lock Haven while two crew members shovel
Digging with a mini excavator on one of our Lock Haven jobs.

When to call a pro or the building department

  • Any footing for a house, addition, garage or attached deck. These usually need a permit, and the inspector may want to see the holes before the pour.
  • Soft clay, wet ground, fill or a high water table.
  • Rock or ledge above the frost line.
  • Heavy loads such as a hot tub or a roof on a deck.
  • Any digging at all: call 811 first so utilities get marked. We call before every job.

If you’d like the deck drawn with post spacing, beam sizes and footing sizes on paper before anyone digs, our online deck design plans lay it out for you or your builder.

Frequently Asked Questions

How deep should deck footings be?

At least 12 inches below undisturbed ground. A deck attached to the house also needs its footings below the local frost line, while a freestanding deck isn’t held to the frost rule under the 2021 IRC, though your building department may still require it.

How deep should footings be for a garage?

An attached garage follows the house: 12 inches minimum and below the frost line. A detached light-frame garage or shed of 600 square feet or less, with eaves 10 feet or lower, is exempt from frost protection; a bigger one is not.

What size footing do I need for a 6×6 deck post?

It depends on the deck area the post carries and your soil, not the post size. At 40 psf, a post holding 40 square feet needs a 16-inch round footing on clay, 14 on sand and 12 on gravel.

Can a footing sit on fill dirt?

Only if it’s engineered fill. Otherwise the IRC requires footings on undisturbed natural soil, so dig through loose fill until you reach it.

Sources: ICC, 2021 IRC R403.1 and Table R403.1(1); ICC, 2021 IRC R403.1.1 Minimum size; ICC, 2021 IRC R403.1.4 Minimum depth; ICC, 2021 IRC R403.1.4.1 Frost protection; ICC, 2021 IRC Table R401.4.1 Soil bearing values; ICC, 2021 IRC Table R301.2; ICC, 2021 IRC R507.3 Deck footings; ICC, 2021 IRC Table R507.3.1 Deck footing size; ICC, 2021 IRC R507.3.2 Deck footing depth; ICC, 2021 IRC R507.3.3 Deck frost protection; Sonoco, Sonotube Builder's Tube brochure

Groundwork Design Co. · designed by builders

Get the slab, walk or pad planned right

Our online plans size patios, walks and pads, set the pitch and spell out the base, so your concrete or paver contractor bids the same job. From $349.

See design packagesTry our free calculators

In central PA? We pour and build flatwork. See our concrete work.

Written and reviewed by Thayne Muthler, owner of Muthler Landscaping & Construction (PA HIC #PA212584). How we check facts: editorial policy.